Bula, we had to attend a breakdown at the school ,the head teacher contacted me through viber that the system was not giving power ,when i checked the fault the inverter was giving red light, i have to check the mate for the alarms that was showing i had to clear the faults, than i was checking the reading for the battery i saw it was 27.1v had to double check with the multimeter yes it was 27.1 and only 1 fx 80 controller was working , we didn't do booster charge since only 1 controller was working, but we spoke with rob on this issue that we will need to replace the FX80 controller once we replace that will booster charge the system and change all 16amps breaker to 4amps and do preventative maintenance on the panels and the system. Vinaka
Bula, attended a break down in school, the whole system was off, when we arrived on site had to check the system voltage it was 45.6v so i had to booster charge the system we charged the the whole day , later in the evening had to remove the booster charge check the voltage it was 51.2v so i had switch on the system the battery percentage was 20% so the head of school said they will leave the power switched off just to bring up the battery percentage to 80% since the weather was gloomy, so the system will be monitored by the head teacher and i have told her on the Load usage on a gloomy weather , we returned back the head teacher was happy for the team being attentive to break downs . Vinaka